Hazardous area Ammonia detector X5
- Simultaneous detection of two different gases
- IONIC sensor with a lifespan of 5+ years
- Two analog outputs (4–20 mA)
- Three dry contact relay outputs
- Color digital display for real-time gas concentration, alarms, and fault indication
- Easy service and maintenance
- Explosion-proof, IECEx / ATEX certified for Zone 1 & 2, Zone 21 & 22
- Manufactured in the UK (Made in UK)
Description
Designed for industrial ammonia (NH₃) detection to ensure worker safety
Suitable for installation in production facilities, storage tanks, refrigeration systems, laboratories, and more.
The detector is equipped with an Ionic Ammonia sensor with a lifespan of over 5 years.
The sensor is resistant to humidity and can operate in low temperatures down to -40°C.
Detection Ranges (Ammonia):
- 0–100 ppm (TOC-102-NH3-1)
- 0–500 ppm (TOC-102-NH3-5)
- 0–5,000 ppm (TOC-102-NH3-50)
Dual Gas Detection Capability
This detector can measure two different gases simultaneously, thanks to its dual-sensor design:
- One sensor dedicated to ammonia
- Second sensor configurable for an additional gas of your choice
The detector features two independent channels, meaning each sensor operates separately—essentially providing two detectors in one unit.
Each channel includes a separate 4–20 mA analog output, allowing easy integration with external systems (e.g., fire detection systems or control systems).
Display & Status Indication
- Real-time gas concentration displayed on a color digital screen
- Green – Normal operation
- Red – Alarm condition
- Orange – Fault
Installation & Safety
- ATEX certified, suitable for hazardous areas (Zone 1 & Zone 2)
- Explosion-proof design
- Remote sensor capability via cable
Example:
For gases with different densities (e.g., hydrogen – lighter than air, LPG – heavier than air), one sensor can be mounted on the detector and the second remotely for optimal detection.
Optional Second Sensor – Supported Gases
- Carbon Monoxide (CO)
- NOx compounds
- Chlorine (Cl₂)
- Sulfur Dioxide (SO₂)
- Oxygen deficiency (O₂)
- Hydrogen Sulfide (H₂S)
- Flammable gases (LEL %) such as methane, hydrogen, propane, LPG, methanol, and more
- Volatile Organic Compounds (VOC)
- Refrigerant gases
PID Sensors (IGD – 30,000-hour lamp life)
- 0–50 ppm (TOC-102-PID05)
- 0–100 ppm (TOC-102-PID01)
- 0–200 ppm (TOC-102-PID02)
- 0–2,000 ppm (TOC-102-PID20)
- 0–5,000 ppm (TOC-102-PID50)
Refrigerant Sensors
- Infrared (IR) 0–2,000 ppm (TOC-102-IRR)
- R1 Group 0–1,000 ppm (TOC-102-R1)
- R2 Group 1,000–10,000 ppm (TOC-102-R2)
Flammable Gas Detection
- Hydrogen 0–1,000 ppm (TOC-102-H2)
- Infrared (IR) 0–100% LEL (TOC-102-IRF)
- Methane IR 0–100% VOL (TOC-102-HIRF)
- MK8 Pellistor 0–100% LEL (TOC-102-MK8)
- Acetylene 0–200 ppm (TOC-102-C2H2)
Oxygen Sensor (Long Life, Lead-Free)
- 0–25% VOL (TOC-102-O2)
Toxic & Specialty Gases
- Boron Trichloride 0–10 ppm
- Carbon Monoxide 0–100 ppm / 0–2,000 ppm
- Carbon Dioxide 0–5,000 ppm / 0–5% / 0–100% VOL
- Hydrogen Sulfide 0–50 ppm / 0–5,000 ppm
- Hydrogen Chloride 0–10 ppm
- Nitric Oxide 0–100 ppm
- Nitrogen Dioxide 0–20 ppm
- Silane 0–10 ppm
- Sulfur Dioxide 0–5 ppm
- Formaldehyde 0–5 ppm
- Carbon Disulfide 0–100 ppm
- Ethylene Oxide 0–10 ppm / 0–100 ppm
- Sulfur Hexafluoride (SF₆) 0–1,000 ppm
Technical Specifications
- Power Supply: 18–32 VDC
- Operating Temperature: -40°C to +55°C
- Sensor Protection: Stainless Steel 316
- Enclosure: Aluminum (copper-free) JB housing, optional Stainless Steel 316
- Cable Entries: 2 × M20 (optional NPT)
- Weight: 1.5 kg
- Dimensions: Ø110 mm × 130 mm height
- Protection Rating: IP66 (dust & water resistant)
- Explosion-proof design